H3R FIRE EXTINGUISHER MODEL C352TS
MODEL C352TS - Halon 1211
Typical use: Cockpit/Cabin
The C352TS can be found on a wide variety of commercial and general aviation aircraft, from Boeings to Cessnas. Similar in size,
Click here for complete listing of H3R Aviation Fire Extinguishers
Shelf Life
The inspection and maintenance requirements for gauged fire extinguishers such as model C354TS, C352TS and A344T per NFPA 10 call for a 6-year maintenance and a 12-year hydrostatic test calculated from the month and year of manufacture. As long as the extinguisher undergoes the maintenance and passes the test it can remain in service.
H3R Aviation calculates the remaining shelf life of its gauged fire extinguishers by comparing the timing of the 6-year maintenance to the month and year of manufacture per the following formula.
(72 months - Months elapsed from manufacture date) / 72 months = Shelf life remaining
For example, if an extinguisher was manufactured in February of 2009 and the current month is June 2009, it has a remaining shelf life of 94%.
(72 months - 4 months) / 72 months = 94%
Отзывы ещё не добавлены